Power series · POWER250

250kVA

Pairs with the genset and lets it run at its sweet spot: the battery takes the peaks and the diesel burns half the fuel.

POWER250

Storage platform

DG hybrid · SEMS3000

Rated energy
153.6 kWh
Rated output
150 kW
Peak power
250 kVA · 210 s
Rated current
217 A

Applications

Construction sitesMiningManufacturingEmergency powerOutdoor eventsConcrete batch plants

One complete system

Everything in one cabinet.

Battery, power conversion, control and protection arrive as one engineered unit: place it, connect it, power up.

01

LFP battery modules

153.6 kWh of lithium-iron-phosphate storage at 90% usable depth of discharge.

02

Transformer-based PCS

Galvanically isolated output that carries motor-start peaks far above the rated load.

03

SEMS3000 EMS

12-inch touch HMI with remote monitoring, source scheduling and fleet-level control.

04

Protected cabinet

IP54 enclosure with integrated fire suppression and intelligent thermal management.

Power series cabinet · modular battery packs

Power series cabinet · modular battery packs

Working modes

One battery.Four modes.

In hybrid mode the generator holds its most efficient 50–80% load band while the battery rides the peaks. Island mode runs the site on battery alone, grid mode charges from the mains, and the EMS switches between them around the clock.

Compatible DG
≤400 kVA
DG load band
50 – 80%
Parallel
Up to 8 units
Ownership cost
Up to −50%

At a glance

Built for the site.

The physical details that matter for transport, placement and connection.

Weight

≈5,000 kg

Dimensions

2250 × 1550 × 2200 mm

System noise

<65 dB

Operating range

−20 to +50 °C

Datasheet

Technical specifications.

POWER250

AC output · on-grid

Rated power
150 kW
Peak apparent power
250 kVA for 210 s · R load
Rated voltage
400 V ±10%
Rated current
217 A
Grid frequency
50 Hz
AC connection
3P + N + PE

AC output · off-grid

Rated power
150 kW
Peak apparent power
250 kVA for 210 s · R load
Rated voltage / frequency
400 V · 50 Hz
THDv (linear load)
≤3%
Power factor
−1 to +1

Battery

Chemistry
LiFePO₄
Nominal energy
153.6 kWh
Working voltage range
600 – 876 V
Nominal charging current
100 A
Nominal discharging current
200 A
Max. discharging current
300 A
Depth of discharge
90%

Compatible generator

Max. apparent power
≤400 kVA
Rated voltage
400 Vac · 3P + N
Rated frequency
50 Hz

General

Parallel capability
Up to 8 units
EMS / HMI
SEMS3000 · 12-inch LCD touch panel
Ingress rating
IP54
Topology
Transformer-based
Operating temperature
−20 to +50 °C
Storage temperature
−40 to +65 °C
Relative humidity
5 – 95% non-condensing
System noise
<65 dB
Cooling
Intelligent thermal management
Fire suppression
Integrated
Altitude
2,000 m
Dimensions (L×W×H)
2250 × 1550 × 2200 mm
Weight
≈5,000 kg
Standards
UN38.3

Next step

Start with your load.

Share the load profile, duty cycle and site conditions. We will size the storage, charging feed and any generator pairing.