Back-up Generators · PKGVE-30

30kVA

Standby power sized to carry the whole load the moment the mains drop, built around a turbocharged industrial engine and a Nidec alternator.

PKGVE-30

Power platform

Eicher (VECV) · Nidec

Prime power
30 kVA
Prime output
24 kW
Rated current
43.3 A
Voltage
400V

Applications

Emergency powerData & telecomsHealthcareIndustryAgricultureRemote sites

One complete system

Everything in one enclosure.

Engine, alternator, control and acoustic canopy are matched as one set: deliver it, connect it, run it.

01

Eicher (VECV) EE483TCII

Turbocharged · direct injection · water-cooled · 3.298 L displacement · 4 cylinders

02

Nidec alternator

Delivers 30 kVA at 400V, 50/60Hz, 3ph+N.

03

Deep Sea Electronics / DEIF Electronic AMF controller

Controller family used on the non-emission standby (VECV/Wardpower 30-160 kVA) line. Monitors engine + generator running parameters and protections, supports AMF, RS232/RS485 Modbus RTU, remote web monitoring.

04

Acoustic enclosure

1.5 mm CRCA acoustic canopy · < 85 dB @ 1 m (ISO 8528-10)

Eicher (VECV) EE483TCII

Eicher (VECV) EE483TCII

The engine

Built aroundthe engine.

Eicher (VECV) EE483TCII drives this set: 3.298 litres, 4 cylinders, turbocharged · direct injection · water-cooled. Rated for 110% for 1 hour in a 12-hour cycle.

Displacement
3.298 L
Cylinders
4
Speed
1500 rpm
Consumption
7.06 L/h

At a glance

Built for the site.

The physical details that matter for access, installation and service.

Weight

1000 kg

Dimensions

2250 x 1020 x 1330 mm

Noise

< 85 dB @ 1 m (ISO 8528-10)

Fuel tank

80 L

Available configuration

  • Anti-condensation heater

    Alternator winding anti-condensation heater.

  • Winding temperature RTD

    Alternator winding temperature RTD sensor.

  • Bearing temperature detector (BTD)

    Alternator bearing temperature detector.

  • RFI suppression

    Radio frequency interference suppression on the alternator.

Datasheet

Technical specifications.

PKGVE-30

Power ratings

Prime power
30 kVA
Prime output
24 kW
Standby power
33 kVA
Standby output
26.4 kW
Rated current
43.3 A
Rated voltage
400V
Frequency
50/60Hz
Phase
3ph+N
Overload rating
110% for 1 hour in a 12-hour cycle
Governing class
A1

Engine

Brand
Eicher (VECV)
Model
EE483TCII
Mechanical output
28.33 kW
Output
38 bhp
Cylinders
4
Arrangement
Inline
Displacement
3.298 L
Aspiration
Turbocharged · direct injection · water-cooled
Speed
1500 rpm
Governor
Mechanical
Starter rating
1.9 kW
Dry engine weight
330 kg

Alternator & control

Alternator brand
Nidec
Controller
Deep Sea Electronics / DEIF Electronic AMF controller
Controller brand
Deep Sea Electronics / DEIF

Fuel & fluids

Fuel tank
80 L
Tank type
Removable · external filling
Consumption at 100%
7.06 L/h
Consumption at 75%
5.33 L/h
Oil sump
13 L
Coolant capacity
15 L

Enclosure & physical

Enclosure
1.5 mm CRCA acoustic canopy
Noise level
< 85 dB @ 1 m (ISO 8528-10)
Silencer
Internal
Lifting
Single point · forklift pockets · 4-point base lift
Dimensions (L×W×H)
2250 x 1020 x 1330 mm
Weight
1000 kg

Reference conditions

Reference conditions
25 °C · 100 kPa · 30% RH
Site altitude
Up to 1000 m
Ambient temperature
Up to 40 °C · radiator rated to 50 °C

Next step

Start with your load.

Share the load profile and site conditions. We will check the rating, tank and panel configuration.